十三层高层住宅楼建筑给排水设计(含CAD图)
十三层高层住宅楼建筑给排水设计(含CAD图)(任务书,开题报告,外文翻译,计算说明书9000字,CAD图纸29张)
摘要
本设计为某13层住宅建筑建筑给排水设计,主要包括生活给水系统、消火栓系统、自动喷淋灭火系统、排水系统和屋面雨水排水系统五个系统。
给水系统采用竖向分区,负一层到二层为低区,由市政管网直接供水; 3层到8层为中区,9层到13层加阁楼层为高区,均采用变频加压供水。采用上行下给的供水方式,由变频无负压调速泵通过生活贮水池直接向中高区管网供水;生活给水管管材选用PP-R聚丙烯塑料管。
建筑室内排水采用污、废水合流制,室外排水采用雨、污分流制。室内污废水重力自流排入室外污水管,地下室污废水采用潜污泵提升至室外污水管,排水立管主要采用单立管螺旋系统,不增设通气立管;屋面雨水采用重力流雨水斗,外排引向室外雨水管网。雨水管采用塑料管。
根据规范,本建筑为住宅楼,属二类高层建筑,负一层地下储藏室为仓库危险I级。消火栓系统、自动喷水灭火系统不分区,消火栓管材采用无缝钢管、喷淋管材采用镀锌钢管。
关键词: 给水系统 排水系统 消火栓系统 自动喷水灭火系统 雨水系统
[来源:http://www.doc163.com]
Abstract
This design is a 13-storey residential building’s water supply and drainage design, mainly including domestic water supply system, hydrant system, automatic sprinkler system, drainage system and roof rainwater drainage system these five systems.
The water supply system is divided into vertical sections, with the negative first floor to the second floor being the low zone, which is directly supplied by the municipal pipe network. Floors 3 to 8 are in the middle zone, floors 9 to 13 and attic are in the high zone, all of which adopt frequency conversion pressurized water supply. The variable frequency non-negative pressure speed regulating pump directly supplies water to the pipe network in the middle and high area through the living storage tank. Domestic water pipes are made of pp-r polypropylene plastic pipes.
The indoor drainage adopts the combined system of sewage and waste water, while the outdoor drainage adopts the split system of rain and sewage. The indoor sewage is discharged into the outdoor sewage pipe by gravity .The basement sewage is lifted to the outdoor sewage pipe by submersible sewage pump. The roof rainwater USES the gravity flow rainwater bucket, the outside drain leads to the outdoor rainwater pipe network. Rain water pipes are made of plastic. [版权所有:http://DOC163.com]
According to the specification, this building is a residential building, which is a second-class high-rise building, and the underground storeroom on the first floor is classified as warehouse risk I. Fire hydrant system, automatic sprinkler system no need to separate areas, fire hydrant pipe adopts seamless steel pipe, spray pipe adopts galvanized steel pipe.
1.1 工程概况
某高层住宅楼建筑共13层加阁楼层,地下室一层,建筑总高度为41.9m,建筑为住宅楼。设计内容有建筑给水系统、排水系统、雨水系统、消防系统,污水处理系统。
市政管网可以提供供水水压为0.2Mpa。
[资料来源:https://www.doc163.com]
目录
摘要 2
Abstract 3
一、工程概况及设计任务 6
1.1 工程概况 6
1.2设计资料 6
1.2.1 建筑设计资料 6
1.2.2 城市给水排水设计资料 7
1.3 工程设计任务 7
二、建筑给水系统 7
2.1 给水方式的选择 7
2.2 给水系统方案的确定 9
2.3 给水管网水力计算 10 [资料来源:Doc163.com]
2.3.1最高用水量 10
2.3.2设计秒流量 11
2.3.3中区给水管网水力计算 12
2.3.4高区给水管网水力计算 14
2.3.5低区给水管网水力计算 15
2.3.6低、中、高三个区总水头损失 17
2.3.7 贮水池 17
2.3.8 水表水头损失计算 18
2.4 设备的计算与选择 20
2.4.1增压设备 20
2.4.2减压设备 22
2.5 管材 22
三、建筑消防系统 23
3.1消防给水系统方案的确定 23
3.2 室内消火栓给水系统 23
3.2.1消防水池 23
3.2.2消防水箱 24
3.2.3消火栓的布置 25
3.2.4消火栓口所需的水压 25
3.2.5校核 27
3.2.6水力计算 28
3.3 自动喷水灭火系统 30
3.3.1自喷系统的布置 30
3.3.2自喷系统水力计算 30
3.3.3喷淋泵的选择 34
3.4 管材 34
四、建筑排水系统 36
4.1 排水方案 36
4.2 排水管道水力计算 36
4.2.1 排水设计秒流量 36
4.2.2 排水管道的水力计算 37
4.3污水提升设备 41
4.4 管材 41
五、建筑雨水排出系统 42
5.1 建筑雨水的排放方式 42
5.2 管道的布置与敷设 42
5.3 雨水系统的水力计算 42
结论 44
致谢 45
参考文献 46 [资料来源:http://doc163.com]